Hybrid Inverter
H3 Smart Series
FOX ESS H3 Smart Three-Phase Hybrid Inverter
The FOX ESS H3 Smart is a three-phase hybrid inverter range designed to manage solar generation, compatible high-voltage battery storage and grid interaction within a single system. Available in models from 5 kW to 15 kW, it combines three independent MPPT trackers, intelligent monitoring and emergency power supply functionality. The H3 Smart can suit larger residential properties and selected commercial installations, with the final configuration determined by electrical demand, solar array design, battery compatibility and site requirements.

Key information
- Product Code
- H3 Smart Series (legacy reference H3-10.0-Smart)
- Brand
- Fox ESS
- Inverter Type
- Three-phase hybrid
- Rated AC Power
- 5–15 kW, model-dependent
- Standard Warranty
- 10 years, subject to Australian warranty terms
- Maximum Efficiency
- Up to 97.9%
- MPPT Trackers
- 3
- Battery Voltage
- 100–800 V
Product overview
Three-Phase Hybrid Energy Management
This page documents the FOX ESS H3 Smart series as a whole. The legacy Decarby catalogue listed H3-10.0-Smart as the product code while describing the full 5–15 kW family. Electrical values that differ by model are shown in the variant tables below and must not be applied across every SKU.
Technical figures follow EN-H3-Smart-Datasheet(AU)-V1.2 (2 July 2025). Australian warranty coverage follows the Fox ESS Inverter Warranty Policy for Australia and New Zealand, which expressly lists the H3-Smart models. Do not mix these specifications with H3 Pro, H3 Plus, H3-E, H1 or AC3 families.
Product features
Three-Phase Hybrid Inverter Technology
The H3 Smart is designed to coordinate solar generation, compatible high-voltage battery storage and three-phase grid interaction in one inverter. That architecture supports self-consumption, grid export and backup circuit design when the complete system is correctly configured.
Final system behaviour still depends on the selected model, battery pairing, switchboard design, network connection rules and site conditions.
Seven Output Variants
AU V1.2 lists seven models: H3-5.0-Smart, H3-6.0-Smart, H3-8.0-Smart, H3-9.9-Smart, H3-10.0-Smart, H3-12.0-Smart and H3-15.0-Smart. Nominal AC output spans 5 kW to 15 kW depending on the variant.
Selecting the correct model requires an assessment of household or site demand, solar array size, battery plans and distribution-network limits. The 10 kW SKU is the legacy reference model for this catalogue page, not a substitute for every other variant.
Three Independent MPPT Trackers
Each H3 Smart model provides three MPP trackers with one string per tracker (1+1+1). Maximum MPPT input current is 20/20/20 A and maximum short-circuit current is 25/25/25 A.
Independent trackers help when roof planes differ in orientation or shading. String design must still stay within the inverter voltage, current and power limits for the selected model.
High PV Input Capacity
Fox ESS publishes both maximum array power and maximum DC input power for each model. Those limits are not the same. For example, the H3-10.0-Smart lists 20,000 Wp maximum array power and 18,000 W maximum DC input power.
Maximum array power describes how much module nameplate capacity may be connected under manufacturer rules. It does not mean the inverter converts that full DC capacity continuously. Oversizing must be designed model by model and checked against local connection requirements.
High-Voltage Battery Integration
The datasheet specifies lithium-ion high-voltage batteries with a 100–800 V operating window, 50 A maximum charge/discharge current and CAN communication.
Compatible Fox ESS high-voltage battery families must be confirmed against current manufacturer documentation for the proposed model and installation. This page does not claim compatibility with every hybrid battery on the market.
Solar Conversion Efficiency
AU V1.2 lists maximum inverter efficiency up to 97.9%, European efficiency of 97.2% and MPPT efficiency of 99.9%. Exact maximum efficiency can vary by model.
These figures describe inverter conversion efficiency under manufacturer test conditions. They are not battery-pack round-trip efficiency and are not a guarantee of annual energy yield.
Emergency Power Supply
EPS backup is supported, with a manufacturer-stated switch time of less than 20 ms and model-specific nominal EPS output power. EPS circuits, battery state of charge, protected loads and switchboard arrangement determine what can actually be supplied during an outage.
EPS should not be treated as a guarantee of whole-home uninterrupted power. Backup design needs a site-specific assessment.
Smart Monitoring
Fox ESS documents remote monitoring through FoxCloud V2.0 via smartphone app or web portal. Communication interfaces listed on the datasheet include Ethernet, EMS (RS485), meter connection, WiLAN (Wi-Fi + LAN + Bluetooth), optional 4G, DRM, ripple control, USB, BMS (CAN) and SG Ready.
Monitoring visibility depends on correct commissioning, network connectivity and the monitoring services enabled for the installation.
Battery Charging and Discharging
Maximum charge/discharge current is listed as 50 A across the series. Marketing material refers to charge/discharge capability of up to 15 kW on larger configurations, but that figure is not a universal rating for every H3 Smart model.
Actual charge and discharge power depends on battery voltage, state of charge, temperature, inverter model limits and the connected battery system. Do not assume every install can deliver 15 kW battery power.
IP65 Outdoor-Rated Enclosure
The inverter is IP65 rated and listed for outdoor use with wall mounting. That rating describes protection against dust and water ingress under manufacturer test conditions.
IP65 does not remove the need for appropriate mounting location, clearances, weather exposure assessment and compliance with Australian installation standards.
Cooling and Operating Temperatures
AU V1.2 lists natural cooling for the 5–10 kW models and fan cooling for the 12 kW and 15 kW models. Operating temperature is -25°C to +60°C, with derating at 45°C.
Noise is listed as less than 40 dB for naturally cooled models and less than 55 dB for fan-cooled models. Adequate ventilation and manufacturer clearances remain part of correct installation.
Electrical Protection Features
Documented protections include PV reverse polarity protection, battery reverse protection, anti-islanding, output short protection, leakage current protection, insulation resistance detection, overcurrent and overtemperature protection, Type II DC/AC surge protection and a DC switch.
AFCI protection is listed as optional on the AU V1.2 datasheet. It should not be described as standard unless the exact supplied variant includes it.
Australian Installation Suitability
H3 Smart installations in Australia must follow manufacturer instructions, AS/NZS wiring and inverter standards, and the relevant distribution network service provider connection rules.
Export limits, phase balance, protection settings and metering requirements can all affect the final design. Decarby designs systems around those local constraints rather than treating the datasheet as a complete installation plan.
Warranty and Support
The AU V1.2 datasheet states a standard warranty of 10 years. The Fox ESS Inverter Warranty Policy for Australia and New Zealand expressly includes the H3-Smart models and provides a standard materials and workmanship warranty of 120 months from installation, but no more than 132 months from manufacture, whichever comes first.
Optional FoxPlus and FoxPro arrangements are described in the inverter warranty policy and are subject to registration and purchase conditions. This page does not invent a performance, throughput or generation warranty for the inverter.
Technical details
FOX ESS H3 Smart Specifications
General
| Model series | H3 Smart |
|---|---|
| Inverter type | Three-phase hybrid inverter |
| Phase | Three-phase (3L/N/PE) |
| AC power variants | H3-5.0 / 6.0 / 8.0 / 9.9 / 10.0 / 12.0 / 15.0-Smart (5–15 kW nominal) |
| Legacy Decarby reference SKU | H3-10.0-Smart |
| Dimensions (W × H × D) | 600 × 450 × 226 mm |
| Net weight | 34 kg |
| Ingress protection | IP65 (outdoor use) |
| Cooling | Natural cooling (5–10 kW); fan cooling (12–15 kW) |
| Operating temperature | -25°C to +60°C (derating at 45°C) |
| Installation | Wall-mounted |
| Standard warranty | 10 years (datasheet); 120 months from install / max 132 months from manufacture (AU inverter warranty policy) |
PV input and AC output by model
| Model | Max array power | Max DC input | Nominal AC power | Max apparent AC | Nominal EPS output |
|---|---|---|---|---|---|
| H3-5.0-Smart | 11,000 Wp | 11,000 W | 5,000 W | 5,500 VA | 5,000 W |
| H3-6.0-Smart | 14,000 Wp | 13,200 W | 6,000 W | 6,600 VA | 6,000 W |
| H3-8.0-Smart | 18,000 Wp | 17,600 W | 8,000 W | 8,800 VA | 8,000 W |
| H3-9.9-Smart | 20,000 Wp | 18,000 W | 9,900 W | 9,900 VA | 10,000 W |
| H3-10.0-Smart | 20,000 Wp | 18,000 W | 10,000 W | 11,000 VA* | 10,000 W |
| H3-12.0-Smart | 24,000 Wp | 22,500 W | 12,000 W | 13,200 VA | 12,000 W |
| H3-15.0-Smart | 30,000 Wp | 22,500 W | 15,000 W | 16,500 VA | 15,000 W |
*Belgian safety footnote on the datasheet requires 10,000 W apparent power to be treated as 10,000 VA where that regulation applies. Maximum array power is not continuous DC conversion capacity. Use only the row matching the supplied model.
PV input (common series values)
| Max PV DC voltage | 1,000 V (max operating voltage 950 V for 1,000 V systems) |
|---|---|
| Nominal PV DC operating voltage | 620 V |
| MPPT voltage range | 120–950 V |
| PV start-up voltage | 140 V |
| Min operating PV voltage | 90 V (power-supply start working voltage footnote) |
| Number of MPP trackers | 3 |
| Strings per MPP tracker | 1 + 1 + 1 |
| Max MPPT input current | 20 / 20 / 20 A |
| Max MPPT short-circuit current | 25 / 25 / 25 A |
| Max MPPT input power | 10,000 / 10,000 / 10,000 W |
Battery
| Supported battery type | Lithium-ion high-voltage battery (manufacturer-specified) |
|---|---|
| Battery voltage range | 100–800 V |
| Min operating battery voltage | 100 V |
| Max charge/discharge current | 50 A |
| Communication | CAN (BMS) |
| Compatible battery families | Confirm against current Fox ESS high-voltage battery compatibility documentation for the selected H3 Smart model |
AC grid
| Rated grid voltage | 400/230 V or 380/220 V, 3L/N/PE |
|---|---|
| Rated frequency | 50/60 Hz |
| Power factor | 1 (adjustable 0.8 leading to 0.8 lagging) |
| THDi | <3% at rated power |
EPS backup
| Nominal EPS output | Model-dependent (see variant table) |
|---|---|
| EPS rated voltage | 400/230 V or 380/220 V, 3L/N/PE |
| EPS transfer / switch time | <20 ms |
| EPS THDv | <3% at linear load |
| Output limitations | Limited by selected model rating, battery state of charge, protected circuits and system design |
Efficiency
| Max inverter efficiency | Up to 97.9% |
|---|---|
| European efficiency | 97.2% |
| MPPT efficiency | 99.9% |
Protection and communication
| Surge protection | Type II (PV) / Type II (AC) |
|---|---|
| Anti-islanding | Active frequency drift with positive feedback |
| Reverse polarity / reverse connect protection | Yes |
| DC switch / isolator | Yes |
| AFCI protection | Optional (not standard on all units) |
| Communication interfaces | Ethernet; EMS (RS485); meter; WiLAN (Wi-Fi + LAN + Bluetooth); 4G optional; DRM; ripple control; USB; BMS (CAN); SG Ready |
| Monitoring | FoxCloud V2.0 |
Manufacturer-listed standards and certifications
Manufacturer-listed protection features (datasheet)
- PV reverse polarity protection
- Battery reverse protection
- Anti-islanding protection
- Output short protection
- Leakage current protection
- Insulation resistor detection
- Overcurrent / overtemperature protection
- Type II DC/AC surge protection
- DC switch
Choosing your inverter
Is the FOX ESS H3 Smart Right for Your Project?
Inverter selection should start with the property and energy goals. Three-phase supply, electrical demand, solar array layout, battery plans, export limits and future electrification all affect whether an H3 Smart model is appropriate and which kW rating to choose.
Decarby designs hybrid systems around those constraints rather than selecting an inverter from a brochure rating alone.
Electrical demand
Peak and continuous loads determine whether a 5 kW, 10 kW or 15 kW model is the better fit.
Solar array design
Roof orientation, string current and array size must stay within the selected model PV limits.
Battery plans
High-voltage battery compatibility, voltage window and charge/discharge needs should be confirmed early.
Network requirements
Local DNSP rules, export limits and protection settings can constrain inverter selection.
Backup requirements
EPS capability depends on protected circuits, battery capacity and complete system design.
Not Sure What System You Need?
You don't need to have the answer before you call us.
Tell us about your home, your electricity use and what you're hoping to achieve. We'll help you work through what makes sense whether that's solar now, solar and battery together, or a system designed so you can add more later.
Practical advice. No sales pressure.
Related products
PRODUCT FAQ
Questions About the FOX ESS H3 Smart
What is the FOX ESS H3 Smart?
It is a three-phase hybrid inverter series from Fox ESS, available in seven models from 5 kW to 15 kW nominal AC output. It is designed to manage solar generation, compatible high-voltage battery storage and grid interaction.
Why does the legacy Decarby page list H3-10.0-Smart?
The older Decarby product code used the 10 kW variant as the catalogue reference while describing the full series. This page keeps H3-10.0-Smart as the legacy reference SKU and documents all seven variants separately so 10 kW values are not applied to every model.
How many MPPT trackers does it have?
Three independent MPP trackers, with one string per tracker. Maximum input current is 20 A per tracker and maximum short-circuit current is 25 A per tracker.
What battery voltage does the H3 Smart support?
AU V1.2 lists a 100–800 V lithium-ion high-voltage battery window with 50 A maximum charge/discharge current and CAN communication. Exact battery compatibility must still be confirmed against Fox ESS documentation.
Does the H3 Smart provide backup power?
Yes, EPS backup is supported with a manufacturer-stated switch time under 20 ms and model-specific EPS ratings. The loads that can be supplied during an outage depend on battery capacity, state of charge, protected circuits and system design.
What efficiency does Fox ESS specify?
AU V1.2 lists maximum inverter efficiency up to 97.9%, European efficiency of 97.2% and MPPT efficiency of 99.9%. These are inverter conversion figures, not battery round-trip efficiency.
What Australian warranty applies?
The datasheet states a 10-year standard warranty. The Fox ESS Inverter Warranty Policy for Australia and New Zealand includes the H3-Smart models and provides 120 months from installation, capped at 132 months from manufacture. Optional FoxPlus and FoxPro terms are described in that policy and are separate from battery warranties.
Is this the same as H3 Pro or H3 Plus?
No. H3 Smart, H3 Pro and H3 Plus are different Fox ESS inverter families with different ratings and documentation. Do not interchange their specifications.
Is AFCI included as standard?
AU V1.2 lists AFCI protection as optional. Confirm whether the exact unit supplied for a project includes AFCI before treating it as a standard feature.
How do I know which H3 Smart model suits my property?
That depends on three-phase demand, solar array design, battery plans, export limits and future electrification. Decarby can assess these factors and advise which model and system configuration may fit.